@inproceedings{c005d3ec87664e3e9345af36cd091e40,
title = "Simulation of adsorber tube diameter's effect on new design silica gel-water adsorption chiller",
abstract = "A new design of silica gel-water adsorption chiller is proposed. The design configuration is composed of two sorption chambers with compact fin tube heat exchangers as adsorber, condenser, and evaporator. Heat and mass recovery were adopted in order to increase the cooling capacity. Numerical modelling and calculation were used to show the performance of the chiller with different adsorber tube diameter. Under typical condition for hot water inlet/cooling water inlet/chilled water outlet temperatures are 90/30/7°C, respectively, the simulation results showed the best average value of COP, SCP, and cooling power are 0.19, 15.88?W/kg and 279.89?W using 3/8 inch tube.",
author = "Nasruddin and A. Taufan and A. Manga and D. Budiman",
note = "Publisher Copyright: {\textcopyright} 2017 Author(s).; 1st International Tropical Renewable Energy Conference: Renewable Energy Technology and Innovation for Sustainable Development, iTREC 2016 ; Conference date: 26-10-2016 Through 28-10-2016",
year = "2017",
month = mar,
day = "28",
doi = "10.1063/1.4979231",
language = "English",
series = "AIP Conference Proceedings",
publisher = "American Institute of Physics Inc.",
editor = "Nofrijon Sofyan",
booktitle = "Renewable Energy Technology and Innovation for Sustainable Development",
address = "United States",
}