TY - JOUR
T1 - Multi-stage heat-pipe heat exchanger for improving energy efficiency of the HVAC system in a hospital operating room
AU - Sukarno, Ragil
AU - Putra, Nandy
AU - Hakim, Imansyah Ibnu
AU - Rachman, Fadhil Fuad
AU - Mahlia, Teuku Meurah Indra
N1 - Publisher Copyright:
© 2020 The Author(s) 2020. Published by Oxford University Press.
PY - 2021/5/1
Y1 - 2021/5/1
N2 - The demands of specific requirements related to thermal comforts, such as temperature, relative humidity, inside air exchange and other factors required in a hospital operating rooms, have necessitated the development of energy-efficient heating, ventilation and air conditioning (HVAC) systems and efficient heat-recovery system using a heat-pipe heat exchanger (HPHE). The experiment was conducted by using HPHEs having three, six and nine rows, with four heat pipes in each row, arranged in a staggered configuration with a variation of fresh-air inlet temperature and velocity. The theoretical analysis was conducted using the ϵ-NTU method for predicting the effectiveness, outlet temperature of the evaporator side and energy recovery of the HPHE. The experimental results indicated that increasing the air-inlet temperature in the evaporator section and the number of rows increased the HPHE effectiveness but increasing the air-inlet velocity reduced the effectiveness. The highest effectiveness of 62.6% was obtained at an air-inlet temperature of 45°C with an air-inlet velocity of 2 m/s and a 9-row HPHE. The energy recovery of the HPHE increased with the number of rows, air-inlet temperature and air velocity in the evaporator section. The ϵ-NTU method can be used as a comparison method in the analysis of heat-recovery systems that apply HPHE air conditioning systems. Heat pipes that utilize cold-air exhaust from a room in an HVAC system can enhance efficiency and reduce emissions.
AB - The demands of specific requirements related to thermal comforts, such as temperature, relative humidity, inside air exchange and other factors required in a hospital operating rooms, have necessitated the development of energy-efficient heating, ventilation and air conditioning (HVAC) systems and efficient heat-recovery system using a heat-pipe heat exchanger (HPHE). The experiment was conducted by using HPHEs having three, six and nine rows, with four heat pipes in each row, arranged in a staggered configuration with a variation of fresh-air inlet temperature and velocity. The theoretical analysis was conducted using the ϵ-NTU method for predicting the effectiveness, outlet temperature of the evaporator side and energy recovery of the HPHE. The experimental results indicated that increasing the air-inlet temperature in the evaporator section and the number of rows increased the HPHE effectiveness but increasing the air-inlet velocity reduced the effectiveness. The highest effectiveness of 62.6% was obtained at an air-inlet temperature of 45°C with an air-inlet velocity of 2 m/s and a 9-row HPHE. The energy recovery of the HPHE increased with the number of rows, air-inlet temperature and air velocity in the evaporator section. The ϵ-NTU method can be used as a comparison method in the analysis of heat-recovery systems that apply HPHE air conditioning systems. Heat pipes that utilize cold-air exhaust from a room in an HVAC system can enhance efficiency and reduce emissions.
KW - effectiveness
KW - energy recovery
KW - heat-pipe heat exchanger
KW - ϵ-NTU
UR - http://www.scopus.com/inward/record.url?scp=85107991059&partnerID=8YFLogxK
U2 - 10.1093/ijlct/ctaa048
DO - 10.1093/ijlct/ctaa048
M3 - Article
AN - SCOPUS:85107991059
SN - 1748-1317
VL - 16
SP - 259
EP - 267
JO - International Journal of Low-Carbon Technologies
JF - International Journal of Low-Carbon Technologies
IS - 2