Effect of ice mass fraction on ice slurry flow for cold energy storage application

F. A. Rayhan, Yanuar, A. S. Pamitran

Research output: Contribution to journalArticlepeer-review

16 Citations (Scopus)

Abstract

The characteristics of ice slurry flows in a pipe are critical due to the potential consequence of pressure drops. This work attempted to conduct an experimental study on ice slurry flow in a horizontally posited circular pipe. This study was conducted on glycol-added (20%) ice slurry with varied ice mass fractions (10%, 15% 20%, 25%, 30%). During experiments, the flow tests were conducted by covering both laminar and turbulent flows. Results of the investigation discovered ice slurry to behave as a Newtonian fluid at mass fraction below 10%, while it also behaved as a non-Newtonian fluid at mass fraction up to 15%. Then, pressure drop was revealed to increase significantly at low-speed settings and high ice mass fractions. To maximize the use of ice slurry as a cold energy storage, therefore, ice mass fraction must be kept at below 20% in a laminar flow.

Original languageEnglish
Pages (from-to)790-794
Number of pages5
JournalEnergy Reports
Volume6
DOIs
Publication statusPublished - Feb 2020

Keywords

  • Flow
  • Ice mass fraction
  • Ice slurry
  • Pressure drop